The Regulatory Reform (Fire Safety) Order 2005 is the main fire safety law in England for almost every building except private homes. It requires the “responsible person” to carry out a fire risk assessment, act on it, maintain fire precautions and keep the arrangements under review. Since 2021 and 2023, further changes have extended and tightened these duties for multi-occupied residential buildings.
This guide explains the Order in plain English: who it applies to, what the responsible person must do, how it is enforced and what has changed. It is general information, not legal advice. If you need an assessment, see our guide to fire risk assessment costs.
What is the Fire Safety Order 2005?
The Order replaced a patchwork of earlier fire certificate rules in 2006. Instead of a certificate issued by the fire service, it puts the duty on the person in control of the premises to manage fire risk themselves. It applies in England and Wales, with some differences in Wales, and Scotland and Northern Ireland have separate laws. This article focuses on England.
Who does it apply to?
The Order applies to non-domestic premises, which includes workplaces, shops, offices, pubs, schools, care homes, hotels and factories, and to the common parts of multi-occupied residential buildings such as blocks of flats and HMOs. It does not apply to a single private home occupied by one household. Since the Fire Safety Act 2021 the Order also makes clear that, in a multi-occupied residential building, the structure, external walls (including cladding and balconies) and the entrance doors to individual flats fall within the fire risk assessment.
Who is the responsible person?
The responsible person is whoever has control of the premises. In a workplace that is usually the employer. In other buildings it is the person who controls them as an owner or in the course of a business, such as a landlord, freeholder, right-to-manage company or managing agent acting for them. There can be more than one responsible person, for example in a shared building, and each must co-operate and co-ordinate with the others. Section 156 of the Building Safety Act 2022 reinforced these duties.
What must the responsible person do?
- Carry out a suitable and sufficient fire risk assessment and keep it under review.
- Take general fire precautions to reduce risk and make sure people can escape safely.
- Provide and maintain fire safety measures, including detection and warning, escape routes and exits, emergency lighting, firefighting equipment and signage.
- Plan for emergencies, with procedures for evacuation and for contacting the fire and rescue service.
- Inform, instruct and train staff, and give relevant information to others who use the premises.
- Look after people at particular risk, including those who are disabled, young or asleep.
- Co-operate and share information with other responsible persons in the same building.
The Order is deliberately general. It tells you what to achieve, not exactly how, so the fire risk assessment is the document that turns it into a plan for your building.
What does “suitable and sufficient” mean?
It is the test every assessment has to meet. In practice, a suitable and sufficient assessment identifies the fire hazards, identifies who might be harmed, evaluates the risk and the existing precautions, and records what needs doing. It should be proportionate to the building, so a small low-risk office needs far less than a block of flats with sleeping residents. A generic template that has never seen your building will rarely meet the test.
What has changed: Fire Safety Act 2021 and 2023 changes
| Change | What it does |
|---|---|
| Fire Safety Act 2021 | Confirms the Order applies to the structure, external walls (including cladding and balconies, windows) and flat entrance doors of multi-occupied residential buildings. |
| Fire Safety (England) Regulations 2022 (in force 23 January 2023) | Adds duties for residential buildings, including fire safety instructions for residents, fire door information and, in buildings over 11 m, quarterly and annual door checks. Further requirements apply to high-rise buildings. |
| Building Safety Act 2022, Section 156 (from 1 October 2023) | Requires the full assessment to be recorded in all circumstances, the assessor’s name and organisation to be recorded, co-operation between responsible persons and information to be shared on handover and with residents. |
A separate requirement for the responsible person to appoint a competent person to carry out the assessment is not yet in force, though government guidance recommends choosing someone with sufficient training, experience or knowledge. Details are in the GOV.UK guidance on Section 156.
Who enforces the Order, and what are the penalties?
In most premises the local fire and rescue authority enforces the Order. In some workplaces, such as construction sites and certain sports grounds, other bodies enforce it. Inspectors can carry out fire safety audits, give advice, issue informal notices, serve enforcement notices, issue prohibition notices that restrict or stop the use of premises, and prosecute. Serious offences can lead to an unlimited fine and, on conviction on indictment, imprisonment of up to two years. The responsible person, not the assessor, carries the legal duty, so using an assessor does not transfer the liability.
How the Order applies in different buildings
- Blocks of flats: common parts, external walls and flat entrance doors, with the additional 2022 and 2023 duties. See our guide to fire door regulations and inspections.
- HMOs: shared areas, with the council’s licensing rules sitting alongside. Our HMO fire safety regulations guide covers this.
- Commercial properties and workplaces: the whole premises, including staff training and emergency procedures.
We carry out assessments across Milton Keynes, Bedford and the Home Counties. Request a fixed-fee quote
Fire Safety Order 2005: frequently asked questions
Does the Fire Safety Order apply to my building?
It applies to non-domestic premises and to the common parts of multi-occupied residential buildings in England. It does not apply to a private home occupied by one household.
Who is the responsible person under the Order?
It is the person who has control of the premises, usually the employer in a workplace or the landlord, freeholder or managing agent in a residential building. There can be more than one responsible person.
Do I need a written fire risk assessment?
Yes. Since 1 October 2023 the responsible person must record the full assessment in all circumstances, not only where there are five or more employees.
What are the penalties for breaching the Order?
Enforcement can range from advice and notices to prohibition and prosecution. Serious offences can lead to an unlimited fine and, on conviction on indictment, up to two years in prison.
Has the Order changed recently?
The Order itself is largely the same, but the Fire Safety Act 2021, the Fire Safety (England) Regulations 2022 and Section 156 of the Building Safety Act 2022 have added duties, particularly for multi-occupied residential buildings.
Written by Ray Amoah, ABBE Level 4, DipFRA, MIFSM, FPA and FIA member, Vigilance Fire Safety. Last updated 25 November 2026. This guide is general information, not legal advice.
Written by
Ray Amoah
Fire risk assessor behind Vigilance Fire Safety (ABBE Level 4, DipFRA, MIFSM, FPA member). Ray carries out every assessment in person.
• Keep reading ——