Fire doors in blocks of flats over 11 metres high must be checked on a set schedule: flat entrance doors at least once a year and fire doors in the common parts at least every three months. These duties came into force on 23 January 2023 under the Fire Safety (England) Regulations 2022. Other buildings have no fixed interval in law, but the fire risk assessment should set one.
This guide explains what the rules require, what an inspector actually looks at, and who is allowed to carry out the checks. It is written for landlords, freeholders, managing agents and employers. Our fire risk assessment service for flats includes fire door checks as part of the assessment.
Which fire door rules apply to you?
| Building | What the law requires |
|---|---|
| Multi-occupied residential building with storeys over 11 m | Check flat entrance doors annually and common-parts fire doors quarterly. |
| Any multi-occupied residential building with two or more sets of domestic premises | Give residents information on the importance of fire doors and fire safety instructions. |
| Non-domestic premises, HMOs and other buildings | No fixed interval in the regulations. The Fire Safety Order requires doors that form part of the fire precautions to be maintained, and your fire risk assessment should set the frequency. |
Since the Fire Safety Act 2021, the structure, external walls and flat entrance doors of multi-occupied residential buildings fall within the responsible person’s fire risk assessment. The details are in the GOV.UK fact sheet on the 2022 regulations.
What is a fire door?
A fire door is a complete assembly: the leaf, frame, hinges, seals, closer, glazing and ironmongery, all installed to match the product’s test evidence. Its job is to hold back fire and smoke for a stated period, commonly 30 or 60 minutes, so that people can leave and the fire stays contained. A door that looks right but has the wrong hinges, a missing seal or a damaged closer may not do that.
What does a fire door inspection look at?
- The certification label or marking. A fire door should be traceable to its rating, though older doors may have lost their markings.
- The gaps. Gaps between the door and frame are usually around 3 mm, with a maximum of about 4 mm, and the bottom gap is normally larger. The exact limits come from the door’s test evidence, so measure against that.
- Seals. Intumescent strips and smoke seals should be present, undamaged and not painted over.
- Hinges. Usually three fire-rated hinges per door, secure, with no missing screws or cracks.
- The closer. The door should close fully and latch from any open position. Springs, hold-open devices and removed closers are common defects.
- Glazing and panels. Fire-rated glass should be intact and correctly beaded.
- Condition. No holes, cuts, cracks, warping or later alterations such as new letterboxes, cat flaps or cable penetrations.
- Signage. “Fire door keep shut” or “keep locked” signs where required, and nothing wedged or tied open.
Who can inspect fire doors?
The law does not name a qualification, but the person carrying out the inspection should be competent for the task. For a quick routine check in a block, a trained member of staff or a managing agent using a clear checklist may be enough. For a formal inspection, or where doors are damaged or of unknown specification, use a qualified fire door inspector or a fire risk assessor with relevant training. Third-party certification of the people who install and maintain fire doors is also available and is worth asking about.
How often should fire doors be checked?
- Over 11 m residential: flat entrance doors annually, common-parts fire doors every three months, as the regulations require.
- Other residential buildings and HMOs: set the frequency in your risk assessment. Many landlords check shared-area doors every few months and after any report of damage. See our guide to HMO fire safety regulations for what councils tend to expect.
- Commercial premises: as part of regular maintenance and at least during each fire risk assessment review.
Record every check: the date, who did it, which doors were looked at, what was found and what was done about it. The record is what shows you have kept the doors maintained.
What if a fire door fails?
Report and prioritise it. Minor defects, such as a worn seal or a loose hinge screw, can often be repaired quickly. A damaged leaf, a missing closer or a door of unknown rating may need replacing. Until the repair is made, treat the risk as live and make sure residents know not to prop the door open. Where a door cannot be fixed straight away, record why and set a firm date. Your fire risk assessment action plan, set by an assessor, is the right place to rank the work. Our cost guide explains what an assessment normally includes.
Fire door signage and resident information
Residents of multi-occupied residential buildings should be told how important fire doors are: that they must be kept shut, must not be wedged open and should not be altered. A simple leaflet or notice in the communal areas helps, and the information should be re-issued when tenants change.
Fire door checklist
- Does the door close fully into the frame from any open position?
- Are the gaps even and within limits?
- Are the seals and strips intact?
- Are all three hinges tight and undamaged?
- Is the glazing, if any, intact?
- Is the door free from holes, cracks or later alterations?
- Is the door shut and not wedged open?
- Has the check been recorded?
We carry out fire door checks as part of our assessments of blocks of flats, HMOs and commercial properties across Milton Keynes, Bedford and the Home Counties. Request a fixed-fee quote
Fire door regulations: frequently asked questions
How often do fire doors need to be inspected?
In multi-occupied residential buildings over 11 metres, flat entrance doors must be checked annually and common-parts fire doors quarterly. For other buildings there is no fixed legal interval, so your fire risk assessment should set one.
Who is responsible for flat entrance fire doors?
The responsible person for the building is responsible for fire safety in the common parts, and since the Fire Safety Act 2021 the flat entrance doors fall within their fire risk assessment. Your lease or tenancy agreement may allocate day-to-day repair, so check it.
What gap is allowed around a fire door?
Usually around 3 mm at the sides and top, with a maximum of about 4 mm, and a larger gap permitted at the threshold. The exact limits depend on the door’s test evidence, so check the manufacturer’s information.
Can a tenant fit their own fire door?
Tenants should not replace or alter a fire door without the landlord’s agreement. A new door must be an appropriately certified fire door installed correctly, otherwise it may not protect the escape route.
Do fire doors need to be kept closed?
Yes. A fire door only works if it is shut when a fire starts. Do not wedge, tie or prop it open. Where a door must be held open, use an approved device that releases on the fire alarm.
Written by Ray Amoah, ABBE Level 4, DipFRA, MIFSM, FPA and FIA member, Vigilance Fire Safety. Last updated 18 November 2026. This guide is general information, not legal advice.
Written by
Ray Amoah
Fire risk assessor behind Vigilance Fire Safety (ABBE Level 4, DipFRA, MIFSM, FPA member). Ray carries out every assessment in person.